Build configurations and capabilities
Electrical Characteristics
Power rating=50 VA up to 150 kVA
Phases=1-PH, 3-PH
Frequency=50/60 Hz
Voltages=Up to 600 Vrms
Terminal Configurations
Copper buss bar
Silicon bronze hardware
Terminal strip
Ring-lug compatibility
Touch-safe configurations
Lexan covers
Bushings
Noise Attenuation
Common
1 MHz=80 dB
10 MHz=55 dB
100 MHz=45 dB
1 GHz=40 dB
Differential (Transverse)
1 MHz=80 dB
10 MHz=55 dB
100 MHz=45 dB
1 GHz=40 dB
Enclosures and weather
NEMA enclosures
NEMA 4: Watertight
NEMA 4X: Same as 4, but stainless steel
Options
Casters
Circuit breakers
EMO switches
Locking devices
Current-limiting
Ring-lug compatibility
Touch-safe barriers
Fuses
GFI's
Noise Cut Transformers and assemblies are specially designed to attenuate both transverse and common mode noise over a broad spectrum of frequencies and were developed to help meet “Power Vaccine Requirements”. These units can be combined with circuit protection, GFI's and/or any number of electromechanical components.
Examples of Noise Cut Transformers
16.8 kVA Noise Cut Transformer
3-Phase, 50/60Hz
Primary=208 Vrms
Secondary=220 Vrms @ 7 Arms
Primary/Secondary circuit breakers
NEMA4 enclosure
NRTL to UL 1561, CE Mark
10.8 kVA Noise Cut Assembly
3-Phase, 50/60Hz
Primary=208 Vrms
Secondary=208/120Vrms @ 30 Arms
Line filter
Seismic floor mounts
NRTL to UL 1561, 508A, CE Mark
7.2 kVA Noise Cut Transformer
3-Phase, 50/60Hz
Primary=208 Vrms
Secondary 1=208 Vrms @ 30 Arms
Secondary 2=120 Vrms @ 6 Arms
Casters
NRTL to UL 1561, 508A, CE Mark